European Assessment Document

    EAD 330387-00-0601 - Glass fibre-reinforced plastic (GFRP) connectors for use in sandwich and element walls made of concrete

    Testing · NAC-037-TLCertification · NAC-026-PPSETA route

    In short

    EAD 330387-00-0601 is the EOTA European Assessment Document for glass fibre-reinforced plastic (gfrp) connectors for use in sandwich and element walls made of concrete. Amstelfy Technical Solutions tests GFRP connectors for sandwich wall panels against this EAD in its ISO/IEC 17025-accredited laboratory in Amstelveen (NAC-037-TL): tension and shear resistance, durability in alkaline environment and creep. The test reports follow the EAD clause structure so a Technical Assessment Body can use them directly for the European Technical Assessment; Amstelfy does not issue ETAs itself. Within its ISO/IEC 17065 scope (NAC-026-PPS) Amstelfy can also act as the product certification body for this product family.

    What the EAD assesses

    EAD 330387-00-0601 assesses glass-fibre reinforced polymer connectors that join the facing layer of a concrete sandwich wall to its load-bearing layer through the insulation, or hold the two shells of a precast element wall together until the core is cast. The connectors replace stainless-steel ties to remove the thermal bridge, but a pultruded or moulded GFRP pin behaves differently from steel: its strength is direction-dependent, it does not yield, it loses strength under sustained load and it is attacked by the alkaline pore water of concrete. The EAD therefore assesses the characteristic resistance to tension and to shear for the connector anchored in both layers across the declared insulation thicknesses, the stiffness of the connection, long-term strength retention in alkaline environment, creep and creep rupture under sustained load, behaviour at the temperature limits and the anchorage detail in each layer.

    Assessment programme

    Connectors are cast into two-layer concrete specimens with the insulation and layer thicknesses to be claimed, so that the free length of the connector between the layers is representative. Tension tests pull the layers apart to fail the anchorage or the connector; shear tests displace one layer parallel to the other, which loads the connector in bending and shear across the gap, and record load against relative displacement. Durability specimens are stored in alkaline solution at elevated temperature for the periods set by the EAD and then tested in tension to establish the residual-strength curve; sustained-load tests at several stress levels give the creep-rupture relationship. Freeze-thaw cycling and tests at the temperature limits complete it.

    What the report states

    The report gives per connector type, insulation thickness and layer thickness the ultimate loads, failure modes (connector rupture, pull-out from a layer, concrete breakout), stiffness values and 5 % fractiles, together with the strength-retention factors from the alkaline and sustained-load series. The TAB combines these into characteristic short-term resistances, long-term reduction factors, connection stiffness and the geometric conditions stated in the ETA.

    Where the result is required

    Precast producers and structural engineers use the ETA to design the ties of sandwich panels for wind, the dead load of the facing layer, thermal bowing and handling, and the connectors of element walls for fresh-concrete pressure during casting, with the design method referenced in the ETA. Products are pultruded pins, grids and plate connectors of GFRP, CE marked under the AVCP system stated in the EAD. The material behaviour parallels FRP reinforcing bars assessed under EAD 260023, and the US route is ICC-ES AC320.

    What we assess

    • tension and shear resistance
    • durability in alkaline environment
    • creep

    Products covered

    • GFRP connectors for sandwich wall panels

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030Yes
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Route to market

    Products covered by an EAD are placed on the EU market with a European Technical Assessment issued by a Technical Assessment Body (TAB), followed by the AVCP tasks of a Notified Body and the manufacturer's Declaration of Performance and CE marking. Amstelfy performs the assessment tests, prepares the test reports in the EAD's clause structure and coordinates the test plan with the TAB; Amstelfy does not issue ETAs.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    No. ETAs are issued by Technical Assessment Bodies designated under the CPR. Amstelfy carries out the assessment tests in its accredited laboratory, prepares the test reports to the EAD's clause structure and coordinates the test plan with the TAB of your choice.

    Glass fibres and some resins degrade slowly in the alkaline pore solution of concrete. To predict strength after decades within a test programme, specimens are immersed in alkaline solution at raised temperatures for defined periods and tested for residual tensile strength; the results at several temperatures are extrapolated to the service temperature with the time-shift approach described in the EAD.

    The free length of the connector between the layers governs its shear and bending behaviour, so the ETA covers only the range of insulation and layer thicknesses tested. The least and most favourable combinations are tested and intermediate thicknesses are interpolated. A change of connector length or anchorage geometry counts as a new product for the assessment.

    In a sandwich wall the connector carries permanent and variable loads for the life of the building, so long-term, thermal and durability data decide the design values. In an element wall it mainly resists the pressure of fresh concrete during casting and keeps the shells aligned, so short-term tension and bending resistance and stiffness at casting age govern. One ETA can cover both.