European Assessment Document

    EAD 330196-00-0604 - Plastic anchors for fixing of external thermal insulation composite systems with rendering

    Testing · NAC-037-TLCertification · NAC-026-PPSETA route

    In short

    EAD 330196-00-0604 is the EOTA European Assessment Document for plastic anchors for fixing of external thermal insulation composite systems with rendering. Amstelfy Technical Solutions tests ETICS plastic anchors (screw-in and hammer-set) against this EAD in its ISO/IEC 17025-accredited laboratory in Amstelveen (NAC-037-TL): tension resistance in concrete and masonry use categories, point thermal transmittance, plate stiffness and durability. The test reports follow the EAD clause structure so a Technical Assessment Body can use them directly for the European Technical Assessment; Amstelfy does not issue ETAs itself. Within its ISO/IEC 17065 scope (NAC-026-PPS) Amstelfy can also act as the product certification body for this product family.

    What the EAD assesses

    EAD 330196-00-0604 assesses the anchors that hold external thermal insulation composite systems against wind suction and dead load: a plastic sleeve with a plate that bears on the insulation board, expanded in the wall by a hammer-set nail or a screw of steel or glass-fibre reinforced plastic. The base material is defined by use categories: A normal-weight concrete, B solid masonry, C hollow or perforated masonry, D lightweight-aggregate concrete and E autoclaved aerated concrete, each with its own characteristic tension resistance. Because the anchor sits in the thermal envelope and under the render, the EAD also assesses the plate stiffness that resists pull-through of the plate, the point thermal transmittance that adds to the heat loss of the wall, the displacement under load, and the durability of the polymer sleeve and the metal element.

    Assessment programme

    Anchors are installed in test members of each claimed category, which for masonry means walls built from named units, using the specified drill, depth and setting procedure. Tension tests load the anchor through the plate as the insulation would, and series after conditioning of the sleeve (elevated temperature, moisture, alkaline contact and installation at low temperature) show the effect of the polymer's behaviour on the expansion. Plate stiffness is measured by loading the plate on a defined bedding and recording load against deflection. The point thermal transmittance is determined by calculation or by hot-box measurement of the anchor in an insulated wall section. Durability of the steel element follows from its coating or material.

    What the report states

    The report gives per category and unit the ultimate tension loads, displacements and failure modes (pull-out, sleeve rupture, plate break), the 5 % fractile and the conditioning ratios, the plate stiffness in kN/mm and the point thermal transmittance in W/K. The TAB turns these into characteristic resistances per use category, minimum embedment and member thickness, and the thermal and stiffness values the ETICS designer needs.

    Where the result is required

    The ETA under this EAD is a prerequisite for the ETICS itself, assessed under EAD 040083, whose wind-load design uses the anchor resistance in the actual wall and the pull-through resistance tested on the insulation. ETICS designers combine the point thermal transmittance with the number of anchors per square metre to correct the U-value. Products are hammer-set and screw-in anchors for EPS, mineral-wool and other board insulation on new and refurbished walls, CE marked under the AVCP system stated in the EAD.

    What we assess

    • tension resistance in concrete and masonry use categories
    • point thermal transmittance
    • plate stiffness
    • durability

    Products covered

    • ETICS plastic anchors (screw-in and hammer-set)

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030Yes
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Other versions on the scope: EAD 330196-01-0604

    Route to market

    Products covered by an EAD are placed on the EU market with a European Technical Assessment issued by a Technical Assessment Body (TAB), followed by the AVCP tasks of a Notified Body and the manufacturer's Declaration of Performance and CE marking. Amstelfy performs the assessment tests, prepares the test reports in the EAD's clause structure and coordinates the test plan with the TAB; Amstelfy does not issue ETAs.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    No. ETAs are issued by Technical Assessment Bodies designated under the CPR. Amstelfy carries out the assessment tests in its accredited laboratory, prepares the test reports to the EAD's clause structure and coordinates the test plan with the TAB of your choice.

    Expansion in concrete, in a solid brick and in the thin webs of a hollow block differs completely, so the EAD defines categories A to E and requires tests in each one claimed; within category C the unit matters, so the ETA names the units tested. Site tests described in the ETA are used where the wall matches no listed category or unit.

    The anchor plate presses on the insulation board and transfers wind suction from board to anchor; a plate that is too flexible lets the board pull over it. Plate stiffness is measured as load per unit deflection of the plate on a defined support and feeds the pull-through resistance assessed in the ETICS ETA. It is a property of the anchor alone.

    Each anchor is a thermal bridge through the insulation. The ETA gives a chi value in W/K per anchor, and the ETICS designer multiplies it by the number of anchors per square metre to add to the U-value of the wall. Anchors with a plastic nail or an insulated head have a lower value than anchors with a plain steel screw.

    Related standards

    All Anchors, fasteners & post-installed rebar testing