European Assessment Document

    EAD 340392-00-0104 - CRM (composite reinforced mortar) systems for strengthening of concrete and masonry structures

    Testing · NAC-037-TLCertification · NAC-026-PPSETA route

    In short

    EAD 340392-00-0104 is the EOTA European Assessment Document for crm (composite reinforced mortar) systems for strengthening of concrete and masonry structures. Amstelfy Technical Solutions tests CRM systems with FRP mesh, connectors and mortar against this EAD in its ISO/IEC 17025-accredited laboratory in Amstelveen (NAC-037-TL): mesh and connector tensile properties, bond and pull-out and durability. The test reports follow the EAD clause structure so a Technical Assessment Body can use them directly for the European Technical Assessment; Amstelfy does not issue ETAs itself. Within its ISO/IEC 17065 scope (NAC-026-PPS) Amstelfy can also act as the product certification body for this product family.

    What the EAD assesses

    EAD 340392-00-0104 assesses composite reinforced mortar systems: a preformed grid of glass or basalt fibre composite with openings of several centimetres, FRP connectors drilled and grouted into the wall, and a mortar layer that embeds the grid and is thick enough to act as a reinforced jacket. CRM is applied to one or both faces of masonry walls, vaults and some concrete members, and works by confining the wall between connected layers rather than by surface adhesion alone. The EAD therefore treats the grid, the connectors and the mortar as components with their own characteristics, then adds system-level tests on the connection between them: pull-out of the grid from the mortar, pull-out of the connector from the substrate, and the connector's tensile and shear capacity. Durability covers the grid and connectors in the alkaline mortar environment.

    Assessment programme

    Grid specimens are tested in tension in both directions on single strands or multi-strand strips, with the cross-section determined from the strand geometry. Connectors are tested in tension and shear, and installed in masonry or concrete blocks for pull-out at the declared embedment. Grid-to-mortar bond is measured by pulling an embedded strand or strip out of a mortar slab. The mortar is tested for compressive and flexural strength and adhesion to the substrate. Where the manufacturer declares them, shear-bond or diagonal-compression tests on strengthened masonry wallets show the system effect. Durability series age grid and connector specimens in alkaline and saline solutions, humidity and freeze-thaw, then repeat the reference tension tests.

    What the report states

    The report lists grid tensile strength, modulus and strain per direction expressed per strand and per metre width; connector tensile, shear and pull-out capacities with failure modes; grid pull-out force from the mortar; mortar strengths; and the retained strength after each ageing condition as a percentage of the reference. Where wallet tests were run, the increase in shear strength or stiffness over the unstrengthened reference is reported.

    Where the result is required

    CRM is used for seismic upgrading of rubble, brick and stone masonry buildings, often alongside the reinforced-plaster traditions of Italy, Greece, Türkiye and the Balkans, and for strengthening of vaults and retaining structures. The ETA values are used in design according to the Italian CRM guideline and national seismic codes, and the connector data interface with the fibre anchor spike assessment of EAD 331668. Manufacturers of pultruded grids also use the same material tests for EAD 260001 profiles.

    What we assess

    • mesh and connector tensile properties
    • bond and pull-out
    • durability

    Products covered

    • CRM systems with FRP mesh, connectors and mortar

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030Yes
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Route to market

    Products covered by an EAD are placed on the EU market with a European Technical Assessment issued by a Technical Assessment Body (TAB), followed by the AVCP tasks of a Notified Body and the manufacturer's Declaration of Performance and CE marking. Amstelfy performs the assessment tests, prepares the test reports in the EAD's clause structure and coordinates the test plan with the TAB; Amstelfy does not issue ETAs.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    No. ETAs are issued by Technical Assessment Bodies designated under the CPR. Amstelfy carries out the assessment tests in its accredited laboratory, prepares the test reports to the EAD's clause structure and coordinates the test plan with the TAB of your choice.

    The EAD does not fix one thickness; CRM layers are typically several centimetres because the grid must be fully embedded with cover on both sides, whereas FRCM plies are only a few millimetres. The thickness declared by the manufacturer is the one used for the system tests and is stated in the ETA.

    Yes, pull-out tests are run in the substrates the ETA will cover, such as solid clay brick, hollow units, tuff or stone with a defined mortar, because the grouted connector relies on the hole wall. Concrete blocks of a declared strength class are used where concrete members are claimed.

    The material data can be reused in part, but the CRM assessment needs tests on the grid as manufactured for the kit, including node strength and strand geometry, and system tests with the kit mortar and connectors. A separate ETA under this EAD is therefore required for the kit.