Test method

    ISO 11925-2 - Reaction to fire tests - ignitability of products subjected to direct impingement of flame - single-flame source test

    Testing · NAC-037-TL

    In short

    ISO 11925-2 - Reaction to fire tests - ignitability of products subjected to direct impingement of flame - single-flame source test. Amstelfy's laboratory determines ignitability with single flame source of construction products (Euroclass E / small flame) according to ISO 11925-2 under its ISO/IEC 17025 accreditation (NAC-037-TL). The method is typically part of initial type testing, ETA test programmes or factory production control verification; results are reported in English for manufacturers across Europe.

    What ISO 11925-2 determines

    ISO 11925-2, adopted in Europe as EN ISO 11925-2, tests how readily a construction product ignites when a small flame touches it, representing a match or a burning droplet. A vertical specimen 250 mm high and 90 mm wide is exposed to a 20 mm propane flame from a burner tilted at 45 degrees, applied to the bottom edge or to the surface, and the observer records whether ignition occurs, whether the flame tip reaches a mark 150 mm above the application point within the observation time, and whether burning droplets ignite filter paper beneath the specimen. In the EN 13501-1 classification system the test alone decides class E, with a 15 second flame application, and it is a prerequisite with a 30 second application for classes B, C and D, which also require the SBI test of EN 13823.

    Specimens, conditioning and procedure

    Specimens are cut from the product in both production directions and conditioned at 23 °C and 50 per cent relative humidity; multilayer products, products with exposed edges and products thicker than the chamber allows are prepared as the standard and EN 13501-1 require. The specimen hangs vertically in the test chamber, the burner is set to the 20 mm flame height and moved into position for surface or edge exposure. Flame is applied for 15 seconds for a class E assessment or 30 seconds for the higher classes, then withdrawn, and observation continues to 20 or 60 seconds respectively. Filter paper under the specimen records flaming droplets. Each exposure and direction is repeated on a set of specimens.

    What the report states

    The report records, per specimen, whether ignition occurred, the time at which the flame tip reached the 150 mm mark, and the occurrence of flaming droplets and ignition of the filter paper. The results are summarised as flame spread Fs reaching or not reaching 150 mm within the observation time and as droplet behaviour. The test report supports a classification report under EN 13501-1, giving class E, the d0, d1 or d2 droplet designation, or eligibility for SBI testing.

    Where the result is required

    The small-flame test underpins class E, the most common declared reaction-to-fire class for sealants, adhesives, membranes, plastic sheets, insulation foams and many composite and timber-based products, and it is the first step towards classes B, C and D for insulation, ETICS kits, sandwich panels and claddings. It appears in the type-testing programmes of harmonised standards such as EN 13163, EN 13164 and EN 14509 and of EADs for ETICS and liquid applied roof waterproofing kits. The classification itself is expressed through EN 13501-1.

    What we assess

    • ignitability with single flame source

    Products covered

    • construction products (Euroclass E / small flame)

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030No
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Route to market

    This test method is used inside initial type testing, ETA assessment programmes and factory production control verification. Amstelfy reports it as an accredited test under NAC-037-TL, either stand-alone or as part of a complete test programme.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    Yes - it is listed on the ISO/IEC 17025 testing scope NAC-037-TL.

    A 15 second application with 20 seconds of observation is the condition for class E: the flame tip must not reach the 150 mm mark in that time. A 30 second application with 60 seconds of observation is required when the product is to be classified B, C or D, in which case the small-flame result must be passed before the SBI test of EN 13823 is run.

    Both can be required. Surface exposure applies the flame to the face of the specimen; edge exposure applies it to the bottom edge and is used when the product has edges that may be exposed in end use, for example boards and membranes with cut edges. The classification standard defines which exposures and how many specimens a product needs.

    Enough to cut sets of 250 mm by 90 mm specimens in both production directions and for each exposure, plus spare material; for thin products this is a modest sheet, for boards a few panels. Products tested on a substrate need that substrate too, and the end-use thickness must be stated because thickness and any backing affect ignition.

    Related standards