Test method

    EN 12667 - Thermal performance of building materials - guarded hot plate and heat flow meter - products of high and medium thermal resistance

    Testing · NAC-037-TL

    In short

    EN 12667 - Thermal performance of building materials - guarded hot plate and heat flow meter - products of high and medium thermal resistance. Amstelfy's laboratory determines thermal resistance (high/medium resistance) of thermal insulation products (MW, EPS, XPS, PIR, PUR, wood fibre) and building materials according to EN 12667 under its ISO/IEC 17025 accreditation (NAC-037-TL). The method is typically part of initial type testing, ETA test programmes or factory production control verification; results are reported in English for manufacturers across Europe.

    What EN 12667 determines

    EN 12667 is the European reference method for the thermal resistance of insulation products: specimens with a thermal resistance of 0.5 m²·K/W or more, measured by guarded hot plate or heat flow meter. The guarded hot plate is an absolute method in which a metered heater, surrounded by a guard at the same temperature, feeds a known heat flow through the specimen; the heat flow meter is a relative method calibrated against reference specimens. Both establish a one-dimensional steady temperature gradient and divide the temperature difference by the heat flux density to obtain resistance. The standard sets the apparatus requirements, specimen conditioning, steady-state criteria and the evaluation of uncertainty, and it is the method the harmonised insulation standards call up for determining declared conductivity at 10 °C.

    Specimens, conditioning and procedure

    Test specimens are cut from product boards to the plate dimensions with faces parallel; compressible products are tested at a defined thickness or under the light plate pressure the standard allows. Specimens are conditioned to constant mass, normally at 23 °C and 50 % relative humidity, and thickness, mass and density are recorded. Plate temperatures are set for a mean of 10 °C unless another temperature is agreed, with a temperature difference inside the permitted range. Measurement continues until the thermal resistance derived from successive readings is stable within the criteria of the standard. The laboratory also notes whether the product shows a thickness effect, in which case EN 12939 applies to the thick-product evaluation. Clients choose the mean temperature set and the number of specimens for a declared-value data set.

    What the report states

    Results are thermal resistance in m²·K/W and, for homogeneous specimens, thermal conductivity in W/(m·K) at the mean temperature, each with its measurement uncertainty, plus thickness, density and conditioning. For CE marking the manufacturer processes a series of such values through the statistical procedure of the product standard to obtain λ90/90, rounded up to the nearest 0.001 W/(m·K), and the corresponding RD per thickness.

    Where the result is required

    EN 12667 is the determination method for thermal resistance and conductivity in EN 13162 (MW), EN 13163 (EPS), EN 13164 (XPS) and the other factory-made insulation standards, including the ageing procedures for XPS, PIR and PUR. It also provides the core conductivity for thermal transmittance of sandwich panels under EN 14509, the thermal resistance of ETICS insulation under EAD 040083, and comparative data in product development.

    What we assess

    • thermal resistance (high/medium resistance)

    Products covered

    • thermal insulation products (MW, EPS, XPS, PIR, PUR, wood fibre)
    • building materials

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030No
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Route to market

    This test method is used inside initial type testing, ETA assessment programmes and factory production control verification. Amstelfy reports it as an accredited test under NAC-037-TL, either stand-alone or as part of a complete test programme.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    Yes - it is listed on the ISO/IEC 17025 testing scope NAC-037-TL.

    Both are permitted and, within their uncertainties, give the same resistance. The guarded hot plate measures heat flow absolutely and carries the lower uncertainty, which is why it is used to characterise reference specimens. The heat flow meter is calibrated against those references and reaches equilibrium faster, so it carries most routine and FPC testing.

    The method returns measured values for individual specimens. The product standard, through its annex on declared values, requires a statistical evaluation of measurements spread over production, giving the λ90/90 limit: the value that 90 % of production meets with 90 % confidence. That limit is rounded up to 0.001 W/(m·K) and the thermal resistance is rounded down to 0.05 m²·K/W.

    Conductivity is measured on a thickness that the apparatus accepts and that represents the product. For light products, in which radiation makes conductivity depend on thickness, the product standard requires the thickness effect to be covered, usually by testing under EN 12939 at thicknesses bracketing the range, so that λD is valid for every declared thickness.

    Related standards

    All Thermal insulation products & hygrothermal test methods testing