European Assessment Document

    EAD 160004-00-0301 - Post-tensioning kits for prestressing of structures

    Testing · NAC-037-TLCertification · NAC-026-PPSETA route

    In short

    EAD 160004-00-0301 is the EOTA European Assessment Document for post-tensioning kits for prestressing of structures. Amstelfy Technical Solutions tests bonded and unbonded PT kits, anchorages, couplers, ducts against this EAD in its ISO/IEC 17025-accredited laboratory in Amstelveen (NAC-037-TL): static load test, fatigue (load transfer and anchorage), load transfer test and assembly and corrosion protection checks. The test reports follow the EAD clause structure so a Technical Assessment Body can use them directly for the European Technical Assessment; Amstelfy does not issue ETAs itself. Within its ISO/IEC 17065 scope (NAC-026-PPS) Amstelfy can also act as the product certification body for this product family. Exclusion on the accreditation scope: Cryogenic test C.2.2 excluded.

    What the EAD assesses

    EAD 160004-00-0301, the successor of ETAG 013, assesses post-tensioning kits as a whole: the tensile elements (strands, wires or bars), the stressing and fixed anchorages, couplers, ducts, fillers such as grout, grease or wax, and the corrosion protection, for internal bonded, internal unbonded and external tendons. The kit is assessed rather than the strand alone, because the governing question is whether the anchorage can develop the strength of the tendon, survive fatigue stress ranges and transfer the force into the concrete without unacceptable cracking. The essential characteristics are therefore resistance to static load, resistance to fatigue, load transfer to the structure, friction and deviation behaviour, the protection levels for durability, and assembly and installation parameters. The accredited scope covers the mechanical test series; the cryogenic test of clause C.2.2 is excluded. Post-tensioning kits fall under AVCP system 1+.

    Assessment programme

    Specimens are complete tendon-anchorage assemblies of sizes selected from the range, the largest unit always included. The static load test stresses the assembly in steps to failure; it must reach a specified fraction of the actual tensile element strength with a minimum elongation. In the fatigue test the tendon is cycled for two million cycles at the prescribed stress range and upper load, with a limit on the cross-section that may fail. In the load transfer test the anchorage is cast into a concrete prism with the minimum bursting reinforcement declared by the manufacturer, loaded in slow cycles while crack widths and strains are measured, then loaded to failure. Assembly, friction, duct, coupler and corrosion-protection checks complete the programme.

    What the report states

    The report gives for each test the load-elongation or load-cycle record, the failure mode and location (wire breaks, wedge slip, anchor head), the achieved fraction of the tensile element strength, elongation at failure, the number of cycles and failed cross-section in fatigue, crack widths and stabilisation in the load transfer test and the ultimate load relative to the characteristic tendon force. The TAB enters the results, the anchorage geometry and the minimum concrete strength and reinforcement into the ETA.

    Where the result is required

    The ETA is the basis for CE marking of the kit under AVCP system 1+ and for its use in prestressed concrete bridges, buildings, silos, tanks, containment structures and strengthening projects designed with EN 1992-1-1 and EN 1992-2. Execution follows EN 13670 and the ETA of the kit, and the specialist company installing it is normally certified under a national scheme. Hollow bar nail kits for ground engineering are assessed separately under EAD 160088.

    What we assess

    • static load test
    • fatigue (load transfer and anchorage)
    • load transfer test
    • assembly and corrosion protection checks

    Products covered

    • bonded and unbonded PT kits, anchorages, couplers, ducts

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030Yes
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Cryogenic test C.2.2 excluded.

    Route to market

    Products covered by an EAD are placed on the EU market with a European Technical Assessment issued by a Technical Assessment Body (TAB), followed by the AVCP tasks of a Notified Body and the manufacturer's Declaration of Performance and CE marking. Amstelfy performs the assessment tests, prepares the test reports in the EAD's clause structure and coordinates the test plan with the TAB; Amstelfy does not issue ETAs.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    No. ETAs are issued by Technical Assessment Bodies designated under the CPR. Amstelfy carries out the assessment tests in its accredited laboratory, prepares the test reports to the EAD's clause structure and coordinates the test plan with the TAB of your choice.

    The EAD requires tests on a selection that covers the range: the largest tendon unit always, plus smaller units chosen so that intermediate sizes can be interpolated, and each anchorage type (stressing, fixed, coupler) and each tensile element (strand, wire, bar) separately. Changes of wedge geometry, anchor head material or bearing plate are treated as new variants.

    The static test proves that the anchorage holds the tendon; it says nothing about the concrete around it. In the load transfer test the anchorage sits in a concrete block with the minimum reinforcement and concrete strength the manufacturer wants to allow, and bursting and splitting cracks are measured under cyclic load before the block is taken to failure. The result fixes the minimum edge distance, spacing and reinforcement.

    Clause C.2.2 concerns tests of the kit at cryogenic temperatures, relevant for tendons in liquefied-gas storage tanks. That series is not on the accredited scope; all other static, fatigue, load transfer and assembly tests are. A manufacturer claiming cryogenic use needs that evidence from a laboratory equipped for it, and the TAB combines the reports.

    Related standards

    All Post-tensioning kits & soil/rock nails testing