European Assessment Document

    EAD 130367-00-0304 - Composite wood-based beams and columns

    Testing · NAC-037-TLCertification · NAC-026-PPSETA route

    In short

    EAD 130367-00-0304 is the EOTA European Assessment Document for composite wood-based beams and columns. Amstelfy Technical Solutions tests wood-based composite beams and columns against this EAD in its ISO/IEC 17025-accredited laboratory in Amstelveen (NAC-037-TL): bending, shear and compression capacity, stiffness and durability. The test reports follow the EAD clause structure so a Technical Assessment Body can use them directly for the European Technical Assessment; Amstelfy does not issue ETAs itself. Within its ISO/IEC 17065 scope (NAC-026-PPS) Amstelfy can also act as the product certification body for this product family.

    What the EAD assesses

    EAD 130367-00-0304, which replaced ETAG 011, assesses prefabricated composite members whose flanges and webs are made of different wood-based materials joined by adhesive: I-joists with solid timber or LVL flanges and OSB, hardboard, plywood or LVL webs, box beams and built-up columns. Because the member is a glued assembly rather than a graded piece of timber, its properties cannot be taken from a timber strength class; they must be derived from tests on the product. The EAD assesses the characteristic bending moment capacity, shear capacity, bearing capacity at end and intermediate supports with and without web stiffeners, axial compression capacity for columns, bending and shear stiffness, web openings where claimed, the durability of the glue line in the claimed service classes, and reaction to fire and fire resistance.

    Assessment programme

    Full-size members are sampled from production across the range of depths and flange sizes to be covered, conditioned to the reference moisture content and tested in the configurations of the timber test standards: four-point bending for moment capacity and bending stiffness, short-span tests for shear and web buckling, bearing tests on short lengths with the support widths and stiffener details claimed, and axial compression on columns of representative slenderness. Load, deflection and failure mode are recorded to failure. Glue-line durability is assessed through delamination or shear tests on the flange-web joint after moisture cycling appropriate to the service class, and the adhesive is checked against the relevant adhesive standard. Characteristic values are derived with the statistical method for timber products.

    What the report states

    The report gives per depth and flange combination the ultimate loads, failure modes (flange tension, web shear, web buckling, bearing crushing, glue-line failure), the derived characteristic capacities in kN and kNm and the mean stiffness values, together with the durability test outcomes. The TAB tabulates in the ETA the characteristic moment, shear, bearing and compression capacities, stiffness and conditions of use, which the designer applies with EN 1995-1-1.

    Where the result is required

    Composite wood-based beams and columns with an ETA are used as floor and roof joists, rafters, purlins, lintels and wall studs in timber-frame housing and light commercial buildings across northern and western Europe; the ETA values feed EN 1995-1-1 design and the span tables of the manufacturer. The product is CE marked under the AVCP system stated in the EAD. Structural timber graded to a strength class and glued laminated timber follow harmonised standards instead of this EAD.

    What we assess

    • bending, shear and compression capacity
    • stiffness
    • durability

    Products covered

    • wood-based composite beams and columns

    Accreditation status

    ActivityStandardAccreditationValidityOn scope
    TestingISO/IEC 17025:2017NAC-037-TLvalid until 2 December 2028Yes
    Product certificationISO/IEC 17065:2012NAC-026-PPSvalid until 31 January 2030Yes
    Validation & verificationISO/IEC 17029:2019NAC-006-VVvalid until 31 January 2030No

    Route to market

    Products covered by an EAD are placed on the EU market with a European Technical Assessment issued by a Technical Assessment Body (TAB), followed by the AVCP tasks of a Notified Body and the manufacturer's Declaration of Performance and CE marking. Amstelfy performs the assessment tests, prepares the test reports in the EAD's clause structure and coordinates the test plan with the TAB; Amstelfy does not issue ETAs.

    How it works

    1. 1

      Send the standard number, product description and intended use

    2. 2

      We confirm the applicable test series, sample quantities and timeline

    3. 3

      Samples are delivered to Veilmeesterweg 20, 1187 ZW Amstelveen (Mon-Fri 09:00-17:00)

    4. 4

      You receive the report in English, written for the TAB, Notified Body, evaluation service or programme operator.

    Frequently asked questions

    No. ETAs are issued by Technical Assessment Bodies designated under the CPR. Amstelfy carries out the assessment tests in its accredited laboratory, prepares the test reports to the EAD's clause structure and coordinates the test plan with the TAB of your choice.

    Harmonised standards exist for graded structural timber, glulam, LVL and wood-based panels as materials, but not for a member assembled from several of them with adhesive, whose capacity depends on the joint, the web buckling behaviour and the stiffener details. The EAD closes that gap by deriving the member properties from full-size tests and placing them in an ETA.

    Enough to derive characteristic values statistically for each property and each depth or flange group: the number per series is set by the statistical procedure for timber products, and the range is covered by testing the extreme depths and interpolating. Large ranges therefore mean several hundred full-size tests, so grouping of similar sections is agreed with the TAB at the start.

    The flange-web joint must stay intact through the moisture changes of the claimed service class. Specimens are cycled through wetting and drying or soaking and are then tested in shear or examined for delamination, and the adhesive itself must comply with the adhesive standard for that service class. Members claimed for service class 2 need the more severe conditioning.

    Related standards

      All Wood-based composite beams & columns testing